Function
code
Name
Description
(setting range)
Factory
Default
Change
PC-51
Multi-speed priority mode
selection
0: Multi-speed does not
have priority
1: Multi-speed priority
1
☆
PC-52
Multi-speed priority
acceleration and deceleration
time selection
0: Acceleration and
deceleration time 1
1: Acceleration and
deceleration time 2
2: Acceleration and
deceleration time 3
3: Acceleration and
deceleration time 4
0
☆
PC-53
Multi-speed PC-00
~
PC-15
unit selection
0: %
1: Hz
0
☆
PC-55
Multi-segment instruction 0
given mode
0: Function code PC-00
given
1: AI1
2: AI2
3: PULSE pulse
4: PID
5: Preset frequency given
(P0-11), UP/DOWN can be
modified
0
☆
Group PD: Torque control
PD-00
Torque command source
selection
0: Digital setting (PD-01)
1: AI1
2: AI2
3: Communication given
4: PULSE pulse frequency
setting
5: MIN (AI1, AI2)
6: MAX (AI1, AI2)
(1-6 option full scale
corresponds to PD-01)
0
★
PD-01
Torque digital given
-200.0%
~
200.0%
150.0%
☆
PD-03
Torque control positive
direction maximum frequency
0.00Hz
~
Maximum
frequency (P0-14)
50.00Hz
☆
PD-04
Torque control reverse
direction maximum frequency
0.00Hz
~
Maximum
frequency (P0-14)
50.00Hz
☆
C
h
a
p
te
r
5
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......