-163-
Chapter 6 Description of Function Codes
Fig.6-10 Three-wire operation mode 2
SB2
FWD
in
v
e
rte
r
DIn
COM/+24V
SB1
K
REV
K
0
1
RUN command
Reverse RUN
Forward RUN
2: Three-wire operation mode
The enable terminal of this mode is Din, the running command is given by FWD, and the dire-
ction is determined by the state of REV.
The stop command is done by disconnecting the Din signal.
SB1: Stop button
SB2: Run button
Din is the multi-function input terminal of
DI1~HDI, and its corresponding terminal
function should be defined as the No. 3
function "three-wire operation control".
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-12
Terminal UP/DOWN change rate
0.01Hz/s
~
100.00Hz/s
1.00Hz/s
☆
Terminal UP/DOWN to adjust the rate of change of the set frequency.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-13
Terminal valid logic 1
00000
~
11111
00000
★
0: High level
1: low level
Ones place: DI1
Tens place: DI2
Hundreds:
3
Thousands:
4
Ten thousand:
5
DI1~DI5 terminal valid level selection.
DI
DI
DI
C
h
a
p