-154-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P4-05
Motor 1 rated frequency
0.01Hz
~
P0-14
50.00 Hz
★
P4-06
Motor 1 rated speed
1rpm
~
60000rpm
P4-01 OK
★
<
1> When the rated power of the motor P4-01<=30KW, P4-4 is 2 decimal points, and when
P4-01>30KW, it is 1 decimal point.
The above function codes are the parameters on the motor nameplate. Whether V/F or vect-
or control is used, the relevant parameters need to be set accurately according to the motor
nameplate.
In order to obtain better V/F or vector control performance, motor parameter tuning is require-
d, and the accuracy of the tuning result is closely related to the correct setting of the motor
nameplate parameters.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P4-07
Motor 1 no-load current
0.01A
~
P4-04<1>
Model is
determined
★
P4-08
Motor 1 stator resistance
0.001
Ω~
65.535
Ω
Model is
determined
★
P4-09
Motor 1 rotor resistance
0.001
Ω~
65.535
Ω
Model is
determined
★
P4-10
Motor 1 mutual inductance
0.1Mh
~
6553.5Mh
Model is
determined
★
P4-11
Motor 1 leakage inductance
0.01Mh
~
655.35Mh
Model is
determined
★
<
1> When the rated power of the motor P4-01>30KW, P4-4 is 1 decimal point, and when P4-
01<=30KW, it is 2 decimal points
<2>When the rated power of the motor P4-01>30KW, add 1 decimal point, and when P4-01<
=30KW, the decimal point is shown in the table
P4-07~P4-11 function code parameters are generally not on the motor nameplate and need
to be obtained through inverter tuning. Among them, "static tuning" can only obtain three par
-
ameters of P4-07~P4-09, and "rotary tuning" can obtain all 5 parameters. value of a function
code.
Note:
After modifying P4-01, the values of motor parameters P4-02~P4-11 will change accordingly.
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......