![Vicruns 2S-0.4G-B User Manual Download Page 292](http://html1.mh-extra.com/html/vicruns/2s-0-4g-b/2s-0-4g-b_user-manual_1013433292.webp)
-291-
Step 1:
P0-28 set to “T to confirm, restore the factory value.
Step 2:
P0-01 is Tto confirm, and then press PRG to exit, and then close the UP Down
terminals. See whether the inverter has forward and reverse running.
Step 3:
Set: P0-06 into 6, multi-step speed is valid.
Step 4:
set F09.30 into 1 and respectively set F06.02 to 4 , F06.03 to 8 and F06.04 to 7.
Close the low-speed switch (the default is S3) and you can see that the frequen-
cy converter runs at 6Hz forward rotation.
Close the high-speed switch (default is S4 terminal) and you can see that the
inverter displays E008 fault.
Close the maintenance speed switch (default is S5 terminal) and you can see
that the inverter E008 fault disappears.
Step 5:
Set F06.02 (S3) to "12” Corresponding to low speed switch Default 10Hz.
F06.03 (S4) is "13” Corresponding to high speed switching 40/50Hz.
F06.04 (S5) is "14” Corresponding maintenance speed switch Speed is set by
parameter F12.06.
Step 6:
Set the Speed
F12.03=20 (corresponding to low speed of 10HZ).
F12.04=80 or 100 (corresponding to high speed of 40/50HZ).
F12.06=? We don't know the exact speed you need for this one (corresponding
to maintenance speed).
Step 7:
set the acceleration and deceleration should be F05.05=0 P0-12/F0-13/
F09.00 / F09.01 /F09.02 /F09.03 / F09.04/F09.05 all set 2.5.
The detailed Solution steps for setting inverter used on Elevator
C
h
a
p
te
r
1
0
Chapter 10 Appendix