Chapter 6 Description of Function Codes
-174-
Group P7: Accessibility and keyboard display
Define the given frequency and acceleration/deceleration time of the inverter when jogging.
The jog process starts and stops according to start mode 0 (P1-00, direct start) and stop
mod-e 0 (P1-13, deceleration stop).
Jog acceleration time refers to the time required for the inverter to accelerate from 0Hz to the
maximum output frequency (P0-14).
Jog deceleration time refers to the time required for the inverter to decelerate from the maxi-
mum output frequency (P0-14) to 0Hz.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-00
Jog running frequency
0.00Hz
~
Maximum frequency
6.00Hz
☆
P7-01
Jog acceleration time
0.0s
~
3000.0s
10.0s
☆
P7-02
Jog deceleration time
0.0s
~
3000.0s
10.0s
☆
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-03
Acceleration time 2
0.0s
~
3000.0s
10.0s
☆
P7-04
Deceleration time 2
0.0s
~
3000.0s
10.0s
☆
P7-05
Acceleration time 3
0.0s
~
3000.0s
10.0s
☆
P7-06
Deceleration time 3
0.0s
~
3000.0s
10.0s
☆
P7-07
Acceleration time 4
0.0s
~
3000.0s
10.0s
☆
P7-08
Deceleration time 4
0.0s
~
3000.0s
10.0s
☆
The acceleration and deceleration time can be selected from P0-23 and P0-24 and the above
three acceleration and deceleration times. Their meanings are the same, please refer to the
related descriptions of P0-23 and P0-24.
The acceleration and deceleration time 1~4 during the operation of the inverter can be select-
ed through different combinations of the multi-function digital input terminals DI. Please refer
to function codes P5-00
~
P5-04.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-09
Hop Frequency 1
0.00Hz
~
Maximum frequency
0.00Hz
☆
P7-10
Hop Frequency 1 Amplitude
0.00Hz
~
Maximum frequency
0.00Hz
☆
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......