-103-
Chapter 5 Function & Parameter Table
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-07
VF field weakening
area current stall
protection factor
50%
~
200%
100%
★
P9-08
Overvoltage stall
allowable rise limit
value
0.0%
~
50.0%
10.0%
☆
P9-11
Fault automatic reset
times
0
~
20
0
☆
P9-12
Fault relay action
selection during
automatic fault reset
0: no action
1: Action
0
☆
P9-13
Fault automatic reset
interval time
0.1s
~
100.0s
1.0s
☆
P9-14
Input phase loss
enable selection
0: invalid
1: Valid
1
☆
P9-15
Output phase loss
enable selection
0: invalid
1: Valid
1
☆
P9-16
Power-on to ground
short-circuit protection
selection
0: invalid
1: Valid
1
☆
P9-17
Undervoltage fault
automatic reset
selection
0: Manual reset is required after
undervoltage fault
1: After the undervoltage fault, the
fault will be reset by itself according
to the bus voltage
0
☆
P9-18
Overvoltage
suppression mode
selection
0: invalid
1: Overvoltage suppression mode 1
2: Overvoltage suppression mode 2
1
★
P9-19
Overexcitation active
state selection
0: invalid
1: Only the deceleration process is
valid
2: The constant speed and
deceleration process is valid during
running
2
★
P9-20
Overvoltage
suppression mode 2
limit value
1.0%
~
150.0%
10.00%
★
C
h
a
p
te
r
5