-69-
Chapter 4 Operation and Display
0
1
F0- 13
Fs>0
Fs=0
Fs>0
Fs=0
0
1
2
2
P0-13
Run command
(panel)
Forward run
command (terminal,
communication)
Frequency
command
Running
direction setting
Forward running
Run in reverse
Run command
in reverse
(terminal,
communication)
Deceleration to stop
Figure 4-22
Schematic diagram of the running direction of the motor
For applications that do not allow motor reversal, please do not use the method of
modifying the function code to change the direction, because the above two func-
tion codes will be reset after restoring the factory defaults. At this time, the functi-
on of No. 50 of the digital input terminal DI can be used to prohibit reverse rotation.
KD600 has a fixed-length control function. The length pulse is collected through
the DI (DI function selection is 30) terminal. The number of pulses sampled by the
terminal is divided by the number of pulses per meter Pb-07, and the actual length
Pb-06 can be calculated. When the actual length is greater than the set length Pb-
05, the multi-function digital switch output "length reached" ON signal.
During the fixed-length control process, the length reset operation can be perfor-
med through the multi-function DI terminal (the DI function selection is 31), and
the specific settings are shown in the following figure.
4.7.7 Fixed-length control mode settings
C
h
a
p
te
r
4