Chapter 5 Function & Parameter Table
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-16
Upper limit
frequency
Lower limit frequency P0-18
~
maximum
frequency P0-14
50.00Hz
☆
P0-17
Upper limit
frequency offset
0.00
~
Maximum frequency P0-14
0.00Hz
☆
P0-18
Lower frequency
0.00Hz
~
upper limit frequency P0-16
0.00Hz
☆
P0-19
Command source
binding selection
Units digit: selection of frequency sourc-
e bound by operation panel command
0: no binding
1: Digital setting frequency
2: AI1
3: AI2
4: Multi-speed
5: Simple PLC
6: PID
7: Communication given
8: PULSE pulse setting (DI5)
Tens place: Terminal command binding
frequency source selection
Hundreds place: Communication
command binding frequency source
selection
Thousands: reserved
000
☆
P0-20
Frequency
Decimal Selection
1: 1 decimal point
2: 2 decimal places
2
★
P0-21
Acceleration and
deceleration time
unit
0: 1 second
1: 0.1 seconds
2: 0.01 seconds
1
★
P0-22
Acceleration and
deceleration time
reference
frequency
0: Maximum frequency (P0-14)
1: Preset frequency (P0-11)
2: Motor rated frequency (P4-05 or A1-
05)
0
★
P0-23
Acceleration time
1
0s
~
30000s(P0-21=0)
0.0s
~
3000.0s(P0-21=1)
0.00s
~
300.00s(P0-21=2)
10.0s
☆
P0-24
Deceleration time
1
0s
~
30000s(P0-21=0)
0.0s
~
3000.0s(P0-21=1)
0.00s
~
300.00s(P0-21=2)
10.0s
☆
C
h
a
p
te
r
5
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......