-175-
Chapter 6 Description of Function Codes
When the set frequency is within the jump frequency range, the actual operating frequency
will run at the jump frequency boundary closer to the set frequency. By setting the jump freq-
uency, the inverter can avoid the mechanical resonance point of the load. This inverter can
set 2 jump frequency points. If two adjacent jump frequencies are set to the same value, this
function will not work at that frequency.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-11
Hop Frequency 2
0.00Hz
~
Maximum frequency
0.00Hz
☆
P7-12
Hop Frequency 2 Amplitude
0.00Hz
~
Maximum frequency
0.00Hz
☆
P7-19
P7-11
P7-10
P7-10
P7-12
P7-12
Time
Output
frequency (Hz)
Fig.6-13 Schematic diagram of hopping frequency
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-15
Forward and reverse dead
time
0.0s
~
3000.0s
0.0s
☆
Fig.6-14 Schematic diagram of forward and reverse dead time
t1
Output frequency (Hz)
Time
(
t
)
Dead-zone
time
Reverse
rotation
C
h
a
p
te
r
6