Function
code
Name
Description
(setting range)
Factory
Default
Change
B5-03
Current limit value during holding
brake
50.0%
~
200.0%
120.0%
★
Before the inverter starts to accelerate from the brake release frequency, that is, before the
brake mechanism is not completely released, the current is limited to this value.
Function
code
Name
Description
(setting range)
Factory
Default
Change
B5-04
Brake pull-in frequency
0.00Hz
~
20.00Hz
1.50Hz
★
After the inverter receives the stop command, it will decelerate and run to the brake freque-
ncy set by B5-04, and run at a constant speed at this frequency, waiting for the output brake
control signal.
Function
code
Name
Description
(setting range)
Factory
Default
Change
B5-05
Brake pull-in delay time
0.0s
~
20.0s
0.0s
★
After the running frequency reaches the brake frequency, delay the brake waiting time set by
B5-05. Then the switch output "brake control" terminal outputs the brake release signal to
control the brake.
Function
code
Name
Description
(setting range)
Factory
Default
Change
B5-06
Holding time of brake pull-in
frequency
0.0s
~
20.0s
1.0s
★
After the switch output "brake control" terminal outputs the brake release signal, keep the tim-
e set by B5-06 to ensure that the brake mechanism is fully closed. Then the inverter blocks
the output and enters the stop state.
C
h
a
p
te
r
6
Chapter 6 Description of Function Codes
-237-