• E = The feedback value is greater than the wake-up value, and the duration exceeds para-
meter B6-04 (wake-up delay), and the PID function restarts.
• F = The feedback value is less than the wake-up value, and the duration exceeds parame-
ter B6-04 (wake-up delay), and the PID function restarts.
Figure 6-33. Wake up diagram
Function
code
Name
Description
(setting range)
Factory
Default
Change
B6-04
Wake up delay
0.0s
~
3600.0s
0.5s
☆
Function
code
Name
Description
(setting range)
Factory
Default
Change
B6-05
Sleep delay frequency output
selection
0~1
0
☆
Set the wake-up delay time, refer to Figure 6-33 for the function.
0: PID automatic adjustment
;
1: Sleep frequency B6-01
.
C
h
a
p
te
r
6
Chapter 6 Description of Function Codes
-240-
B6-03
Time(t)
B6-03
PA-04=1
PA-04=0
C
D
Time(t)
B6-03
B6-03
C
D
B6-04
F
E
B6-04
Set value