Chapter 6 Description of Function Codes
4: Switch between auxiliary frequency source Y and main and auxiliary operation
results
When the multi-function input terminal function 18 (frequency switching) is invalid, the auxilia-
ry frequency Y is used as the target frequency.
When the multi-function input terminal function 18 (frequency switching) is valid, the main and
auxiliary operation results are used as the target frequency.
Tens place: Frequency source main and auxiliary operation relationship:
0: Main frequency source X+Auxiliary frequency source Y
The sum of the main frequency X and the auxiliary frequency Y is used as the target frequen-
cy. Realize the frequency superposition given function.
1: Main frequency source X-Auxiliary frequency source Y
The main frequency X minus the auxiliary frequency Y is the target frequency.
2: MAX (main frequency source X, auxiliary frequency source Y)
Take the maximum absolute value of the main frequency X and the auxiliary frequency Y as
the target frequency.
3: MIN (main frequency source X, auxiliary frequency source Y)
Take the smallest absolute value of the main frequency X and the auxiliary frequency Y as
the target frequency.
When the main frequency source is selected as "digital setting" or "terminal UP/DOWN", the
function code value is the preset frequency of the frequency setting of the inverter.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-11
Preset frequency
0.00Hz
~
Maximum frequency P0-14
50.00Hz
☆
0: The direction is the same, which is the same as the current running direction of the
motor
1: Opposite direction, opposite to the current motor running direction
;
2: Reverse rotation is prohibited, when there is a reverse rotation command, the inver-
ter will decelerate to 0Hz and enter the stop state
;
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-13
Motor running
direction selection
0
~
2
0
☆
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......