Sort
Terminal
Name
Function Description
Digital
input
DI6-COM
Digital input 6
(
Optional accessories:
IO2 card supports DI6, DI7 expansion;
IO1 card supports DI6, DI7, DI8, DI9, DI10
expansion.)
DI7-COM
Digital input 7
DI8-COM
Digital input 8
DI9-COM
Digital input 9
DI10-COM
Digital input 10
Analog
output
AO1-GND
Analog output 1
The voltage or current output is determined by
the DIP switch on the control board (refer to the
bit number of the terminal wiring diagram).
(Optional accessories: IO1, IO2 support AO2
function)
Output voltage range: 0
~
10V
Output current range: 0
~
20mA
AO2-GND
Analog output 2
Digital
output
Y1-CAE
Digital output 1
Optocoupler isolation, bipolar open collector
output
Output voltage range: 0
~
24V
Output current range: 0
~
50mA
Note: The digital output ground CAE and the
digital input ground COM are internally isolated,
but the CAE and COM have been externally
short-circuited at the factory (the Y terminal is
driven by +24V by default). When the Y terminal
is to be driven by an external power supply, the
external short connection between CAE and
COM must be disconnected. (Optional
accessories: IO2 supports Y2 function)
Y2-CAE
Digital output 2
FM
High-speed
pulse output
Programmable optocoupler isolation, open
collector output
The highest frequency: 50KHz; when the
collector is open-circuit output, it is consistent
with the Y1 specification.
Output voltage range: 0/24VDC, output current
range: 50mA