Chapter 4 Operation and Display
The KD600 inverter provides a variety of terminal control modes. The terminal co-
mmand mode is determined by the function code P5-11, and the input port of the
start-stop control signal is determined by the function code P5-00~P5-04. For the
specific setting method, please refer to the detailed explanation of function codes
such as P5-11, P5-00
~
P5-04.
Example 1:
It is required to use the toggle switch of the inverter as the start-stop switch of the
inverter, connect the forward running switch signal to the DI2 port, and the reverse
running switch signal to the DI4 port. The method of use and setting is as follows.
P0 04=1
.
.
P5-11=0
P0-04=1
Control switch
SW1
SW2
DI
1
DI
2
DI
3
DI
4
DI
5
.
COM
P5-00
P5-01
P5-02
P5-03
P5-04
1
2
.
..
RUN/
positive
RUN/
opposite
Run forward
Run in reverse
Two-wire
mode 1
Terminal
command
Run
command
Function
code
Port
Set value
Terminal
command method
Command
source selection
Figure 4-8
Schematic diagram of terminal control start and stop
In the above control mode, when the SW1 command switch is closed, the inverter
runs forward, and when the SW1 command switch is off, the inverter stops; and
when the SW2 command switch is closed, the inverter runs in reverse, and when
the SW2 command switch is off, the inverter runs. The inverter stops; SW1 and
SW2 are closed at the same time, or open at the same time, the inverter will stop
running..
Example 2:
It is required to use the key solenoid of the inverter as the start-stop switch of the
inverter, connect the start button signal to the DI2 port, the stop button signal to
the DI3 port, and the reverse run button signal to the DI4 port. The use and setting
methods are as follows:
C
h
a
p
te
r
4
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......