Chapter 4 Operation and Display
-62-
P1-00=2, the method is only applicable to the induction asynchronous motor load.
Pre-exciting the motor before starting can improve the fast response characterist-
ics of the asynchronous motor and meet the application requirements that require
a relatively short acceleration time. The frequency curve of the starting process is
as follows.
Figure 4-12
Schematic diagram of pre-excitation startup
Frequency f
P1-00=0:
Pre-excitation start
P0-16 Upper
limit frequency
Time t
Run command
Pre-
excitation
time
P1-05 Start
frequency
holding time
P1-04 Start frequency
P0-23 Acceleration time
P1-04=0.00Hz
P1-05=0.0S
P1-07=0.0S
Frequency f
P1-00=0:
Pre-excitation start
P0-16 Upper
limit frequency
Time t
P0-23 Acceleration time
Run command
Pre-
excitation
time
There are two stop modes of the inverter, namely deceleration stop and free stop,
which are selected by function code P1-13.
4.6.3 Stop mode
制动时间
减速时间
Frequency f
Frequency f
Running
frequency
P1-13=1: Free stop
P0-24
deceleration time
P1-14 Start
frequency
of DC braking
at stop
P1-17 DC
braking time
at stop
Time t
Time t
Stop order
Stop order
Running
frequency
P1-13=1: Free stop
Figure 4-13
Schematic diagram of shutdown
C
h
a
p
te
r
4