Chapter 3 Installation
-34-
C
h
a
p
te
r
3
3.4.1 Control terminals and wiring
RA
RB
RC COM DI6
DI7
DI8
GND TEMP AI3 AO2 DI9 DI10
Y2
RA
RB
RC AO2
DI6
COM GND
DI7
IO1 expansion card
IO2 expansion card
Figure 3-10
Three-phase 380V/660V 4.0KW above expansion card control terminal
Sort
Terminal
Name
Function Description
Power
supply
+
10V-GND
External
+10V power
supply
P10V power supply to the outside, the
maximum output current: 10mA
Generally used as working power supply of external
potentiometer, potentiometer resistance range:
1~5k
Ω
24V-COM
External
+24V power
supply
P24V power supply to the outside,
generally used as the working power supply of
digital input and output terminals and external
sensor power supply,
Maximum output current: 200mA
Analog
input
AI1-GND
Analog input
terminal 1
1. Input voltage range: DC0
~10V
2. Input impedance: 100KΩ
AI2-GND
Analog input
terminal 2
1. Input range: DC0~10V/4~20mA, determined by
the CL3 DIP switch on the control board, the factory
is voltage mode.
2. Input impedance: 100kΩ for voltage input, 500Ω
for current input.
(
Optional accessories: IO1 supports AI3 function)
AI3-GND
Analog input
terminal 3
Digital
input
DI1-COM
Digital input 1 1. Optical coupling isolation, compatible with bipolar
input, switch by DI DIP switch, the factory is NPN
mode
2. Input impedance: 3.3k
Ω
3. Voltage range for level input: 9~30V
4. HDI5 can be used as high-speed input port, the
maximum input frequency is 50KHz
DI2-COM
Digital input 2
DI3-COM
Digital input 3
DI4-COM
Digital input 4
DI5-COM
Digital input 5
3.4.2 KD600 inverter control terminal function description