Chapter 6 Description of Function Codes
-202-
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-01
PID digital setting
0.0
~
100.0%
50.0%
☆
When PA-00=0 is selected, the target source is given by the keyboard. This parameter needs
to be set.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-02
PID given change time
0.00s
~
650.00s
0.00s
☆
The PID given change time refers to the time required for the actual PID value to change from
0.0% to 100.0%.
When the PID given changes, the actual value of the PID given will not respond immediately.
Instead, it changes linearly according to the given time, preventing the given mutation from
occurring.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-03
PID feedback source
0
~
7
0
☆
0: AI1
1: 2
2: AI1-AI2
3: Communication given
4: PULSE pulse given
5: AI1+AI2
6: MAX(|AI1|,|AI2|)
7: MIN (|AI1|,|AI2|)
This parameter is used to select the feedback signal channel for the process PID.
The feedback amount of the process PID is also a relative value, and the setting range is
0.0% to 100.0%.
AI
Function
code
Name
Description
(setting range)
Factory
Default
Change
PA-04
PID action direction
0
~
1
0
☆
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......