![Vicruns 2S-0.4G-B User Manual Download Page 44](http://html1.mh-extra.com/html/vicruns/2s-0-4g-b/2s-0-4g-b_user-manual_1013433044.webp)
-43-
Chapter 3 Installation
C
h
a
p
te
r
3
C. Y1 digital output terminal:
When the digital output terminal needs to drive the relay, an absorption diode should
be installed on both sides of the relay coil, and the driving capacity is not more than
50mA. Otherwise, it is easy to cause damage to the DC 24V power supply.
Note: The polarity of the absorption diode must be installed correctly, as shown in
Figure 3-15, otherwise when the digital output terminal has output, the DC 24V power
supply will be burned out immediately.
DI wiring mode 3 :
No external power supply is used when the DI
DIP switch is in PNP mode
A
C
D
riv
e
r
24V
DI1
(
)
Default FWD
DI2
(Default
REV)
DI3
DI4
HDI5
DI6---DI10
Expansion Card)
(
COM
Shielded cable
grounded at
one end
DI wiring mode 4 :
Use an external power supply when the
DI DIP switch is in PNP mode
A
C
D
riv
e
r
24V
DI1
(
)
Default FWD
DI2
(Default
REV)
DI3
DI4
HDI5
DI6---DI10
Expansion Card)
(
COM
Shielded cable
grounded at
one end
-
+
DC-30V
Figure 3-14
Wiring diagram of digital input terminals in four different modes
CME
Y1
24V
electric relay
Diode
AC Driver
COM
Control terminal
external shorting piece