The count value needs to be collected through the DI (DI function selection is 28)
terminal. When the count value reaches the set count value Pb-08, the multi-func-
tion digital switch output "set count value reached" ON signal, and then the counter
stops counting.
When the count value reaches the designated count value Pb-09, the multi-func-
tion digital switch value outputs the "designated count value reached" ON signal,
and the counter continues to count at this time, and the counter stops until the "set
count value".
4.7.8 How to use the inverter count function
Figure 4-25
Counting mode function code setting
=
=
Count pulse
Count reset
P5-00~P5-04=28
(count pulse input)
P5-00~P5-04=29
(count reset)
Pb-09(spec
-
ified count)
U1-12
(count value)
Pb-08
(set count)
Clear
Reset
F6-00
~
F6-02= 30
(designated count arrival)
P6-00~P6-02=29
(set count arrival)
Reset
After the
specified count
is reached, the
digital port is
set to 1
After the set count
is reached, the
digital port is set to 1
Fb
-
09
=
11
U1
-
12
=
11
1
2
3
10
11
12
U1
-
12
=
0
19
20
21
Fb
-
08
=
20
U1
-
12
=
20
1
2
Count pulse output
Count reset input
The specified count
reaches the output
Set count arrival output
U1-12: count value
Ø
Notice:
Ø
The specified count value Pb-09 should not be greater than the set count value Pb-08.
Ø
When the pulse frequency is high, the DI5 port must be used.
Ø
The digital ports of "set count arrival" and "specified count arrival" cannot be reused.
Ø
In the RUN/STOP state of the inverter, the counter will continue to count, and will not
stop counting until the "set count value".
Ø
The count value can be kept when power off.
Ø
Feedback the count reaching switch output signal to the inverter stop input terminal,
which can be made into an automatic stop system.
C
h
a
p
te
r
4
Chapter 4 Operation and Display
-71-
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......