Chapter 5 Function & Parameter Table
Function
code
Name
Description
(setting range)
Factory
Default
Change
P5-07
DI8 terminal
function
37: Control command switching terminal 2
38: PID integral pause terminal
39: Frequency source X and preset
frequency switching terminal
40: Frequency source Y and preset
frequency switching terminal
41: Switch between motor 1 and motor 2
42: reserved
43: PID parameter switching terminal
44: Speed control/torque control switching
45: Emergency stop
46: External parking terminal 2
47: Deceleration DC braking
48: This running time is cleared
49: Two-wire/three-wire switch
50: Inversion prohibited
51: User-defined fault 1
52: User-defined fault 2
53: Sleep Input
(
Optional accessories:
IO2 card supports DI6, DI7 expansion;
Io1 card supports DI6, DI7, DI8, DI9, DI10
expansion. )
0
★
P5-08
DI9 terminal
function
0
★
P5-09
DI10 terminal
function
0
★
P5-10
DI terminal filter
time
0.000
~
1.000s
0.010s
☆
P5-11
Terminal command
method
0: Two-wire type 1
1: Two-wire type 2
2: Three-wire type 1
3: Three-wire type 2
0
★
P5-12
Terminal UP/
DOWN change rate
0.01Hz/s
~
100.00Hz/s
1.00Hz/s
☆
P5-13
Terminal valid logic
1
0: High level
1: low level
Ones place: DI1;
Tens place: DI2;
Hundreds: DI3;
Thousands: DI4;
Ten thousand: DI5
00000
★
C
h
a
p
te
r
5