7.4 Quick start test run, set it when quick start and stop are required,
otherwise skip this step
Reduce the motor acceleration time (for example, set it to 1 second), change the
speed loop and current loop PI parameter settings, and press the run key to che-
ck whether the motor can quickly accelerate to the set frequency.
Chapter 7 Synchronous Motor Open Loop Vector (SVC) Commissioning Instructions
-247-
C
h
a
p
te
r
7
7.5 Load and run
After the above 5 steps, you can run the motor with load and use the inverter
normally.
Note:
Loading or changing the moment of inertia of the system, if the system response
cannot achieve the expected effect, it is necessary to adjust the two parameters
P3-04 and P3-06 appropriately. If you replace it with another motor, you generally
need to set the rated frequency and rated current of the motor, and then perform
parameter identification.