Chapter 6 Description of Function Codes
This parameter is used to determine the resolution of all frequency-related function codes.
1: 1 decimal point;
2: 2 decimal places.
In order to meet the needs of various fields, KD600 provides 3 kinds of acceleration and dec-
eleration time units, namely 1 second, 0.1 second and 0.01 second.
0:1 second
1:0.1 second
2: 0.01 seconds
Note:
When modifying this function parameter, the number of decimal points displayed by the
4 groups of acceleration and deceleration time will change, and the corresponding accelera-
tion and deceleration time will also change. Special attention should be paid during the applic-
ation process.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-21
Acceleration and
deceleration time unit
0
~
2
1
★
This parameter is used to define the reference frequency of acceleration and deceleration
time, and its meaning is shown in Figure 5-2:
0: maximum frequency (P0-14);
1: Preset frequency (P0-11);
2: Motor rated frequency (P4-05 or A1-05)
.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-22
Acceleration and
deceleration time
reference frequency
0
~
2
0
★
<
1> is the range of acceleration/deceleration time unit P0-21=1, when P0-21=0: 0s
~
30000s;
when P0-21=2: 0.00s
~
300.00s;
Function
code
Name
Description
(setting range)
Factory
Default
Change
P0-23
Acceleration time 1
0.0s
~
3000.0s<1>
10.0s
☆
P0-24
Deceleration time 1
0.0s
~
3000.0s<1>
10.0s
☆
C
h
a
p
te
r
6
-134-
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......