-173-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P6-15
AO1 output upper limit
P6-13
~
100.0%
100.0%
☆
P6-16
The upper limit corresponds to
AO1 output
0.00
~
10.00V
10.00V
☆
P6-17
AO2 output lower limit
-100.0%
~
P6-19
0.0%
☆
P6-18
The lower limit corresponds to the
AO2 output
0.00V
~
10.00V
0.00V
☆
P6-19
AO2 output upper limit
P6-17
~
100.0%
100.0%
☆
P6-20
The upper limit corresponds to
AO2 output
0.00
~
10.00V
10.00V
☆
The above function codes define the corresponding relationship between the output value
and the analog output. When the output value exceeds the set maximum output or minimum
output range, it is calculated by the upper limit output or the lower limit output.
When the analog output is current type output, 1mA current corresponds to 0.5V voltage. In
different applications, the analog output corresponding to 100% of the output value is differe-
nt. As shown in Figure 6-12 below, there are two different linear graphs a and b.
AO
F6-16=10V
F6-14=1V
F6-14=0V
F6-13=0
.
0
%
F6-15=80
.
0
%
F6-15=100
.
0
%
a
a
b
Corresponding
settings
Figure 6-12. Corresponding relationship between the upper and lower limits of analog output
Function
code
Name
Description
(setting range)
Factory
Default
Change
P6-26
Main relay T off delay
0.0s
~
3600.0s
0.0s
☆
P6-27
Main relay R off delay
0.0s
~
3600.0s
0.0s
☆
P6-28
Y1 low level output delay
0.0s
~
3600.0s
0.0s
☆
It is used to set the delay time of the inverter to different output state changes when the Y ter
-
minal state changes or the relay output state changes.
C
h
a
p
te
r
6