OIM Keypad
The SP600 keypad allows for drive setup,
parameter adjustment, monitoring and
drive diagnostics.
Operator Interface Module (OIM)
Start-Up
Parameters
Control Src
Sel
Diagnostics
Display
Memory
Storage
Device
Select
User
Display
By Groups
Changed Params
P Numbers
Speed Ref A Sel
Logic Source Sel
Password
Load Frm Usr Set
Save to User Set
Reset Defaults
Active User Set
Language
Function Keys
Reset Display
Display Video
Display Timeout
Monitor
Device Identity
Fast PwrUp Mode
Contrast
Set Wrt Prot PW
Set Acc Lvl PW
Set Access Lvl
QuickStart
Motor Data
Configure I/O
Ref Setup
Speed Limits
Input Voltage
Motor Tests
Done
ESC/
PROG
Press
Press
Press
to move between menu items
to select a menu item
to move 1 level back in the menu structure
ESC/
PROG
Logout
Menu options
dependent upon
devices connected.
Press
to move between icons
OIM Version
Device Version
View Fault Queue
Device Items
Status Info
Fault Info
Tech Support
Optional
Remote Keypad
RE4LCD-PNL
To use as control
source, set P89 and
P90 = DPI Port 2
NOTE: This material is not intended to
provide operational instructions.
Appropriate Reliance Electric Drives
instruction manuals precautions should be
studied prior to installation, operation, or
maintenance of equipment.
Quick Start
OIM Quick Start Menu
The Quick Start Parameters can be
accessed via the keypad menu icon. Once
into the selection list the following
parameters can be set to configure the
drive to the installed motor.
1) QuickStart
••
Stop Mode A (Ramp)
••
Motor NP FLA (Drive Dependant)
••
Minimum Speed (0.0 Hz)
••
Maximum Speed (60.0 Hz)
••
Accel. Time 1 (10.0 sec.)
••
Decel. Time 1 (10.0 sec.)
••
Speed Reference A select (OIM)
••
Digital IN2 Select (Start)
(Defaults)
The default configuration is defined as:
Drive Voltage rating = Motor Voltage
Start/Stop control = OIM
Speed Reference = OIM
Control Mode = Sensorless Vector
If the drive default configuration is to be
used for initial startup then the above
parameters are the only settings required.
If the user needs to customize the drive
configuration different than the default
setting, then the user should verify
parameter settings accessible throughout
start-up menu.
2) Input Voltages
••
200/240, 400/480, and 575 VAC,
based on model number
3) Motor Nameplate Data
••
Motor Power Units
••
Motor Power
Quick Start (cont.)
3) Motor Nameplate Data con’t
••
Motor FLA
••
Motor Volts
••
Motor Hertz
••
Motor RPM
4) Motor Tests
••
Direction
••
AutoTune
5) Speed Limits
••
Minimum, Maximum
••
Direction Limit
••
Stop Mode
6) Reference Setup
••
OIM Keypad, Terminal Block,
Network, Other
7) Configure I/O
••
Digital Inputs/Outputs
••
Analog Outputs
Control Mode
(P53) Torque Perf Mode
Control performance can be selected
from:
••
Sensorless Vector (default)
Highest performance mode of control
••
SV Economize
Sensorless Vector with energy saving
••
Custom V/Hz
Basic open loop control. Multi-motor
application
••
Fan/Pump: V/Hz
Provides for a Fan load V/Hz curve
ATTENTION: Rotation of the motor in an
undesired direction can occur during this
procedure Autotune (61) = Rotate Tune
(2). To guard against possible injury and/or
equipment damage, it is recommended that the motor be
disconnected from the load before proceeding.
!
START-UP
Quick Start
Quick Start
Instructions
Instructions
Wiring
Power Up
Parameter Setting
Reliance Electric Drives
SP600 AC Variable Frequency
Inverter - 1/2 to 20 HP
6SP Series Model Numbers
Quick Start Instructions:
A quick reference to some basic
configurations and drive features.
Summary of Contents for Reliance electric SP600 Series