Automation Tab
Revised 2017-08-31
Data Logger
Drawing No. LP0997-C
- 182 -
Sixnet
®
Series SN/RAM
®
6000 & RAM 9000 Software Manual
Options - Yes/No
Toggle
Enable from IODB:
Toggle logging based on IODB register (optional field).
For example: if set to DI42, Points will only be recorded if register DI42 is high.
Save Destination
: Destination for the log files. The available options are Internal or SD Card.
Internal
will configure your logs to be stored internally on the device. These can be downloaded through
the Web UI or with gatherstats
SD
Card
(if applicable) will configure your logs to be stored on the SD Card (if present)
Logs will be created in this folder: sdcard/datalogs/
Write Period(s)
: How often a data log record will be created (in seconds)
Recommended: Relative to the rate of change you expect from the logged points
When to Write Data Log Record
: There are two options that are paired with the write period. This setting will
control what conditions create a data log record.
Write a record every period:
If the Write Period is 60 seconds, this will create a new data log record every
60 seconds consistently.
Write when data changes, and periodically:
The IODB list is sampled every second, and if changes are
detected a record is created. In addition, a record will also be created every Write Period of time (60
seconds in this example).
Recommended: Relative to the rate of change you expect from the logged points
Log File Size (KB)
:
Log file size (per file) in Kilobytes
Max: 10240 KB (10MB)
Min: 1 KB
Recommended: 2048
Log Rotation Count
: The number of logs that will be kept in rotation
E.g., when the current log fills up, the oldest is removed, and a new log is started. If the number of logs in
rotation exceeds this value, the oldest is removed
Recommended: 5
Zip-compress Log Files
:
Compress log files using zip
This will reduce storage space by 80%-90%
Password for Zip Files
:
Encrypt zip-compressed log files using this password.
Data Logs Delivery Method
:
Select the delivery method for generated data logs; None, Email, FTP or Both.
Email Recipient
:
When selected enter an email address destination for the logs. Multiple email addresses
may be entered by separating them with a
comma
.
Note:
No spaces are allowed in this field.
Note:
The Email Client service must be configured independent from the Datalog before emails can
be sent successfully.