Revised 2017-08-31
Appendix B
Drawing No. LP0997-C
IODB Status Module
Sixnet
®
Series SN/RAM
®
6000 & RAM 9000 Software Manual
- 279 -
Appendix
B
IODB
Status
Module
The IODB status module is a set of IODB registers that are reserved for system use to collect device based
information and make that information available to be polled by any head end or SCADA server appliances via
Modbus based I/O transfers.
These registers are created as Analog OUT registers as not to interfere with any on board I/O or other commonly
used register types.
Frequency Legend:
Rare = 30 minutes, Sometimes = 5 minutes, Often = 30 seconds, Quickly = 5 seconds,
Rapidly = 1 second
Register type is Analog Out and the initial register offset is 1000.
System
Status
Index
Name
Description
Frequency
Notes
1001
Serial_Number_UINT16_A
First 4 digits, UINT16
Rare
16 digit field saved as 4, 4-digit numbers
1002
Serial_Number_UINT16_B
Next 4 digits
Rare
1003
Serial_Number_UINT16_C
Next 4 digits
Rare
1004
Serial_Number_UNIT16_D
Last 4 digits
Rare
1005
Serial_Number_UINT64_A
UINT64 format; LSW
Rare
16 digit field saved as a single UNT64,
Little Endian, LSB First.
1006
Serial_Number_UINT64_B
Rare
Serial Number = (R (Reg1006 *
2^16) + (Reg1007 * 2^32) + (Reg1008 *
2^48)
1007
Serial_Number_UINT64_C
Rare
1008
Serial_Number_UINT64_D
Rare
1009
Model_Number
4 digit model number
Rare
No prefixes or suffixes
1010
Firmware_Version
3 digit number
Rare
425=4.25, 325=3.25
1011
Date_Year
Year, 4 digit number
Rapidly
1012
Date_Month
Month, 1-12
Rapidly
1013
Date_Day
Day, 1-31
Rapidly
1014
Date_DayOfWeek
Day, 1-7
Rapidly
Sunday=0
1015
Date_DayOfYear
DOY, 1-365
Rapidly
1016
Time_Hour
Hour, 0-23
Rapidly
Current Time
1017
Time_Min
Minute, 0-59
Rapidly
1018
Time_Second
Second, 0-59
Rapidly
1019
Uptime_Days
Days, 0-9999
Rapidly
Time since last reboot
1020
Uptime_Hours
Hours, 0-23
Rapidly
1021
Uptime_Minutes
Minutes, 0-59
Rapidly
1022
Uptime_Seconds
Seconds, 0-59
Rapidly
1023
CPU Load
% CPU Load
Quickly
1061
Onboard_Temp
Onboard-Temp, in C
Often