Analog Input
Click on the
Analog Input
button and the following dialog window appears:
Analog Input Filtering:
The table below explains the filtering (integration) options on the analog inputs. The
faster the integration time, the quicker the channels will be sampled. However, quicker samples will render less
accurate readings. For most accurate readings, select the slower sample/filtering settings.
Temperature Reporting:
Choose from 1°C, 0.1°C, 1°F and 0.1°F. When set for 1°C or F, the temperature is
reported as whole degrees and if set for 0.1°C or F, the reported value is the temperature multiplied by 10 and
reported as an integer.
Channel:
A channel is a physical I/O point that can be either analog or digital.
Modbus Address:
This field indicate the register addresses for each channel. Configuration must be
sequential. Addresses are fixed sequentially from the base address.
Input Type:
Select the type of signal that will be connected to the input.
Integration Time
Samples/Second
(1 Channel)
Notes
3ms/channel
320
Best
for
high
speed
reporting
and
lower
accuracy
6ms/channel
160
12.5ms/channel
80
25ms/channel
40
50ms/channel
(default)
20
Best
for
50/60Hz
noise
rejection
and
higher
accuracy.
100ms/channel
10
200ms/channel
5