Revised 2017-08-31
Automation Tab
Drawing No. LP0997-C
DNP3
Sixnet
®
Series SN/RAM
®
6000 & RAM 9000 Software Manual
- 205 -
Define Highest Register Address
Configure DNP3 Points:
If option is set to No, then no Floating Inputs are mapped as DNP3 points. If set to
Yes, the Highest Register Address field is shown to enter a Highest Register Address value.
Highest Register Address (Required):
This field is used to show or set the highest register address to map
DNP3 points.
Default Deadband
Enter Default DeadBand Value:
Values outside this deadband generate events. The deadband parameter
sets how event data is generated by your module as a DNP3 slave device.
For example:
The Analog Input deadband being set to a value of 1000 will report all of the points as being
class 3 data (as set by the “Analog Input class” parameter being set to 3) and it will generate an event
every time an analog input changes by a value of 1000 or more. This Analog Input deadband can be set to
any value between 0 to 32767 (generate an event when the value changes by 32767).
Default Class Assignment
Default Object 31 - Frozen Analog Input:
This field is activated on both Levels 2 and 2+. It’s used to
determine if a DNP3 point will generate events. In case a DNP3 point generates events (Object2 Binary
Change Events) then it should be associated to a class (Class 1, Class 2 or Class 3), otherwise it should be
associated to None. By default all DNP3 Points don’t generate events, this feature should be modified by the
user.
Default Object 32 - Analog Change Event:
This field is activated on both Levels 2 and 2+. It’s used to
determine if a DNP3 point will generate events. In case a DNP3 point generates events (Object2 Binary
Change Events) then it should be associated to a class (Class 1, Class 2 or Class 3), otherwise it should be