127
Reading Data with the READ DATA Bit
Section 5-3
Program Example
The work bit R1 is used to begin writing.
5-3
Reading Data with the READ DATA Bit
This section explains the procedures for reading data allocated to the operat-
ing memory area from the PCU using the READ DATA Bit (word n+1, bit 13).
A program example is also provided.
Note
1.
Data can be read while pulses are being output, but not while data is being
written or saved. If attempted, it will result in a multiple start error (error
code 8000).
2.
When transferring data using READ DATA, the data must be transferred in
data units. Data transfer should not start or end part-way through the data.
For example, with X axis sequence #0, the data unit becomes three words,
in addresses 1000 to 1002. If the transfer is started or ended part-way
through, a read transfer words error (error code 8320) or read transfer
source address error (error code 8321) will be generated.
5-3-1
Outline
When the READ DATA Bit (word n+1, bit13) in the operating memory area is
turned ON, consecutive addresses data is read from the CPU to the DM or
EM Area according to the number of read words, the read source address, the
read destination area, and the read destination word designated in the operat-
ing data area.
For an outline, refer to
5-2 Writing Data with the WRITE DATA Bit
. With data
reading, 772 words of data in consecutive addresses can be read at one time.
DIFU
R1
MOV
#0004
D00400
200814
MOV
#000D
D00401
MOV
#01F4
D00402
R1
Write switch
Work bit
Data Transferring Flag
MOV
#112C
D00403
200112
END
Set total number of words to
be written to PCU to "4."
Set the setting area for the
speed data to "000D" (DM Area).
Set DM the beginning word in the
DM Area for setting the speed to
"01F4" (500; transfer source).
Set beginning address for the
data area for when speed is writ-
ten to the PCU to "112C" (des-
tination address).
WRITE DATA
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...