145
Transferring Data with CX-Position
Section 5-7
Operating Memory Area
When the SAVE DATA Bit (word n+1, bit 14) is turned from OFF to ON, all
parameters and data are saved to flash memory.
5-6-3
Timing Chart for Saving Data
Data cannot be saved and transferred at the same time. Attempting to do so
will result in a multiple start error (error code 8000). It is also not possible to
save data while pulses are being output. The following diagram is a timing
chart for saving data.
When the data saving operation has been completed, the Data Transferring
Bit (word n+8, bit14) is turned from ON to OFF.
5-7
Transferring Data with CX-Position
It is possible to use the CX-Position Support Software to read, write and save
data, and to monitor the operating status of the PCU.
Outline
CX-Position is software that can be used for setting all kinds of data used by a
PCU as well as for monitoring the operating status of the PCU.
Creating and Transferring
Data
Refer to the CX-Position Operation Manual (W433) for details on its operation.
While CX-Position is used to download data, or to save data to flash memory,
the Data Transferring Flag will be ON.
Note
Do not carry out transfer operations from more than one CX-Position for the
same PCU at the same time. There is a probability of the data transfer not
being completed successfully, and of abnormal operation resulting.
Name
Model
Operating
memory area
Bit
Contents
SAVE DATA
NC4
@
3
NC2
@
3
NC1
@
3
n+1
n+1
n+1
14
Starts saving
data at the ris-
ing edge.
Data Transfer-
ring Flag
NC4
@
3
NC2
@
3
NC1
@
3
n+8
n+4
n+2
14
1: Data is being
saved
0: Power up or
restart; saving
completed;
saving unsuc-
cessful
SAVE DATA
(n+1, bit14)
Data Transferring Flag
(n+8, bit 14)
Normally 1 to 2 s
(30 s max.)
Downloading (or saving)
from CX-Position
Data Transferring Flag
(n+8, 14)
Downloading
Completion
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...