46
Wiring
Section 3-5
An origin search operation cannot be completed unless the positioning com-
pleted input signal turns ON after positioning has been completed.
Note
The values in parentheses apply for the CJ1W-NC413 and CJ1W-NC433.
3-5-4
Wiring Precautions
Operational errors such as dislocation can occur in most electronic control
devices if they are subjected to electronic noise from nearby power lines or
loads. Recovery from such errors is usually very difficult and time consuming.
To avoid such noise-generated operational errors and improve system reliabil-
ity, always observe the following precautions in wiring the system.
Be sure to use the sizes and materials indicated in the specifications when
connecting power lines and cables.
Power lines (e.g., AC power supply, motor power line) and control lines (e.g.,
pulse output lines, external I/O signal lines) must be wired separately. Never
put these lines into the same duct or make them into a single bundle.
• Attach a multi-layer ceramic capacitor of a thickness of less than 1
µ
F to
the pulse output power supply to improve noise resistance.
• Do not use a 24-V DC or 5-V DC power supply for pulse output in com-
mon with the power supply for other I/O.
• Use shielded cable for control lines.
• Connect the shielded cable to the frame ground at both the PCU and the
driver.
Position Control Unit
24-VDC
power supply
A11/B11
+
OMRON R88D-GT
–
38
39
INP
560
Ω
(680
Ω
)
4.7 k
Ω
(5.6 k
Ω
)
INPCOM
Servo Drive
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...