43
Wiring
Section 3-5
3-5-2
Connecting Input Signals
!Caution
If the switching capacity is too low it may cause damage to the switch. Con-
nect a switch with a switching capacity of at least 5 mA for each input.
With N.C. inputs, be sure to connect a power supply for unused terminals and
turn them on.
This section shows examples of connecting interrupt, emergency stop, and
CW/CCW limit input signals.
The input section has both N.O. and N.C. inputs. Either can be used depend-
ing on the axis parameter settings. For details regarding axis parameters,
refer to
4-4 Axis Parameter Area
.
Depending on the setting of the origin search operation pattern, the point at
which the origin proximity signal or the CW/CCW limit signal changes from
ON to OFF is used as the timing for origin signal detection. In this case, use a
sensor with no chattering, such as a photoelectric sensor, for the input. Using
a switch with contacts may cause the position of the origin to be displaced due
to chattering. For details on setting operation patterns for origin searches,
refer to page 153.
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...