Writing Data with the WRITE DATA Bit
Section 5-2
5-2-2
Data Writing Procedure
1,2,3...
1.
Set the common parameters. (Refer to
4-3 Common Parameter Area
.)
m:
Set the operating data area either to DM or to EM.
m+1:
Set the beginning word of the operating data area (I).
m+2:
Designate the axis parameters.
2.
Power up again or restart.
The data for the common parameters set in 1 above is enabled.
3.
Set the operating data area.
I:
Total number of words (Hex) for the data to be written to the PCU.
I+1:
The area in the CPU Unit (DM/EM) where the data is set.
I+2:
Beginning word address (Hex) of the area in the CPU Unit’s DM or
EM area where the data is set.
l+3:
Beginning address (Hex) of PCU data area where data is to be
stored.
4.
Set data.
Set data to be written to the PCU in the area (in the DM or EM Area) spec-
ified by words I to I+2.
5.
Execute WRITE DATA.
Turn the WRITE DATA Bit (word n+1, bit 12) from OFF to ON.
The operations in (1) and (2) above are required when using the PCU for the
first time or when modifying the common parameter settings.
5-2-3
Data Settings Required for Writing Data
Beginning Words of Memory Areas
The beginning words of the operating memory area, the operating data area
and common parameter area used for a PCU are determined (or set) accord-
ing to the following.
• Beginning word of the operating memory area, n = CIO 2000 + 10
×
unit
number
• Beginning word of the common parameter area, m = 100
×
unit
number
• Beginning word of the operating data area, l, is specified in m and m+1.
Word
Name
Bit
Reference
m
Operating data area
designation
00 to 15
SECTION 4
m+1
Beginning word of
operating data area
00 to 15
m+2
Axis parameter
designation
00 to 15
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...