Procedure for Replacing a PCU
Section 12-4
12-4-2 PCU Parameters and Operating Data Saved to PCU’s Flash
Memory
1,2,3...
1.
Make a note of the unit number of the PCU to be replaced.
2.
Save the parameters and operating data for the PCU to be replaced to a
floppy disk or a hard disk using CX-Position.
When not using CX-Position, first read the parameters and operating data
to the PLC’s DM Area using a data transfer bit or the IORD instruction, and
then transfer the contents of the DM Area to a floppy disk or hard disk using
CX-Programmer.
3.
Turn OFF the power supply.
4.
Make a note of the way in which the PCU is wired. (It is recommended that
the cables are labelled.)
5.
Replace the PCU, and reconnect the wiring as before.
6.
Set the unit number for the PCU.
7.
Turn ON the power supply to the PLC.
8.
Transfer the saved parameters and operating data to the PCU using CX-
Position. If the parameters and operating data have been saved in the
PLC’s DM Area, first transfer them to the PLC using CX-Programmer, and
then transfer them to the PCU using a data transfer bit or the IOWR in-
struction. After transfer, write the parameters and data to PCU’s flash
memory.
9.
Turn the PLC power OFF and back ON.
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...