Outline
Section 7-1
7-1
Outline
Position control is carried out by setting positions, speeds, and acceleration/
deceleration times each time in the operating data area specified by the com-
mon parameters.
The positions and speeds set in the operating data area by the MOVL instruc-
tion are output to the Position Control Unit (PCU) automatically at I/O refresh
time. Data transfer is not required.
Start is executed by the ABSOLUTE MOVEMENT command (for the X axis:
word n, bit 03) allocated to the operating memory area (in the CIO Area) or
when the RELATIVE MOVEMENT command (for the X axis: word n, bit 04) is
turned ON.
• The ABSOLUTE MOVEMENT command determines the position from the
absolute position in relation to the origin. With the ABSOLUTE MOVE-
MENT command, a present position unknown error (error code 5040) will
be generated if the origin has not been established.
• With the RELATIVE MOVEMENT command, position control is based on
the amount of relative movement from the present position. Relative
(See note 1.)
Operating data area
Position (rightmost word)
Position (leftmost word)
Speed (rightmost word)
Output at I/O refresh time
Output at I/O refresh time
Absolute movement (word n, bit 03)
(See note 2.)
Relative movement (word n, bit 04)
Input at I/O refresh time
Note
1. This is the area for NC413.
2. When it is the X axis.
I: Beginning word address of area designated in common parameters.
n: Beginning word address of work bit determined when the PCU's unit number was set.
Speed
CW position
(1)
(2)
1. Set the data in the operating data area.
2. Start operation using the operating memory area.
Status
Input at I/O refresh time
Speed (leftmost word)
Acceleration time (rightmost word)
Acceleration time (leftmost word)
Deceleration time (rightmost word)
Deceleration time (leftmost word)
Present position (rightmost word)
Present position (leftmost word)
Operating memory area
PCU
CIO Area
Status
PLC
Summary of Contents for CJ1W-C113 - REV 02-2008
Page 2: ...CJ1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 27: ...xxviii Conformance to EC Directives 6 ...
Page 43: ...16 Control System Principles Section 1 7 ...
Page 47: ...20 Basic Procedures Section 2 ...
Page 139: ...112 Examples of Parameter Settings Section 4 9 ...
Page 173: ...146 Transferring Data with CX Position Section 5 7 ...
Page 223: ...196 Sample Program Section 7 7 ...
Page 259: ...232 Sample Program Section 8 10 ...
Page 293: ...266 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 369: ...342 Reading Error Information with CX Position Section 11 8 ...
Page 385: ...358 Common Parameter Area Appendix C ...