896
7 APPLICATION INSTRUCTIONS
7.17 Pulse Related Instructions
Outputting pulses at regular intervals
PLSY
This instruction outputs the pulses of the specified frequency to the output module.
■
Execution condition
Setting data
■
Descriptions, ranges, and data types
*1 Only labels assigned to device (Y) can be used.
■
Applicable devices
*1 Only Y can be used. Note, however, that it can be used only within the range of the number of I/O points (the number of points that can
access I/O modules).
Ladder
ST
ENO:=PLSY(EN,s,n,d);
FBD/LD
Instruction
Execution condition
PLSY
Operand
Description
Range
Data type
Data type (label)
(s)
Frequency, or the start number of the device containing the
frequency
1 to 100
16-bit signed binary
ANY16
(n)
Number of outputs, or the start number of the device
containing the number of outputs
0 to 65535
16-bit unsigned binary
ANY16
(d)
Device used for pulse output
Bit
ANY_BOOL
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(s)
(n)
(d)
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
(s)
(n)
(d)
EN
ENO
s
d
n
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......