11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
1217
11
Time proportioning
S.DUTY
This instruction outputs ON and OFF by changing the ON/OFF ratio in a given cycle in proportion to the input data (0 to
100%).
■
Execution condition
Setting data
■
Description, range, data type
■
Applicable devices
■
Input data
Ladder
ST
ENO:=S_DUTY(EN,s1,s2,d1,d2);
FBD/LD
Instruction
Execution condition
S.DUTY
Operand
Description
Range
Data type
(s1)
Input data start device
Refer to "Input data".
Single-precision real
number
(d1)
Block memory start device
Refer to "Block memory".
Word
(s2)
Empty string specification
(Specify "" in ladder. Specify '' in ST or FBD/LD.)
String
(d2)
Loop tag memory start device
Refer to "Loop tag memory".
Word
EN
Execution condition
Bit
ENO
Execution result
Bit
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, R, ZR,
RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(s1)
(d1)
(s2)
(d2)
Operand: (s1)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
E1
Input value
(
MV)
-999999 to 999999 [%]
Single-precision
real number
User
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
(s1)
(d1)
(s2)
(d2)
EN
ENO
d1
d2
s1
s2
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......