18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.6 Reading the Module Status Information of an Intelligent Device Station
1625
18
■
Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■
Control data
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z LT, LST,
LC
LZ
K, H E $ J
U
(J/U)
J(P).S
INFST
RD
G(P).
SINFS
TRD
(s)
(d1)
(d2)
Operand: (s)
Device
Item
Description
Setting range
Set by
+0
Error completion type
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data at completion with an error in (s)+12 and later.
• 1: Set data at completion with an error in (s)+12 and later.
(2) Arrival check time setting (bit 8)
• 0: 1s units
• 1: 100ms units
0000H
0080H
0100H
0180H
User
+1
Completion status
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
System
+2
Own station channel
Specify the channel to be used by own station.
1 to 32
User
+3 to +4
Not used
System
+5
Target station number
Specify the station number of the target station.
1 to 120
User
+6
Not used
System
+7
Number of resends
■
Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s)+8.
• 0 to 15 (times)
■
At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
0 to 15
User/
system
+8
Arrival monitoring time
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s)+7.
■
When "0" is specified in bit 8 of (s)+0
• 0: 10s
• 1 to 32767: 1 to 32767s
■
When "1" is specified in bit 8 of (s)+0
• 0: 10s
• 1 to 65535: 1 to 65535
100ms
0 to 65535
User
+9 to +10
Not used
System
+11
Clock setting flag
The validity status (valid or invalid) of the data in (s)+12 and later is stored. Note that
the data in (s)+12 and later is not cleared even when the instruction is completed
successfully.
• 0: Invalid
• 1: Valid
System
b15
0
0
(2) (1)
b7
b8
b0
…
…
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......