11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■
Output type (1)
The output type is determined by the combination of control mode (MODE) and operation type (TYPE) as follows.
■
Loop stop processing (2)
The following processing is performed according to the SPA status of the alarm detection (ALM).
■
SV count-up processing (3)
SV count-up is performed every execution cycle (
T) according to the following expression.
SV'=SV+
T
■
MVPGS operation (4)
MV
PGS
operation is shown below.
■
Output processing (5)
The output processing conditions are shown below.
*1 If the MHI or ERRI of the disable alarm detection (INH) is set to 1, the output upper limit alarm (BB2) and the MHA of the alarm detection
(ALM) are set to 0.
*2 If the MLI or ERRI of the disable alarm detection (INH) is set to 1, the output lower limit alarm (BB3) and the MLA of the alarm detection
(ALM) are set to 0.
Control mode (MODE)
Operation type (TYPE)
Operation
MAN, CMB, CMV, LCM, LCA, LCC
Operation stop with the current SV and MV
AUT, CAB
0
Hold type operation
1
Return type operation
CAS, CCB, CSV
Cyclic type operation
SPA status
Processing details
1
The loop stops.
When the loop stops or the number of operation constant break points is 0, the following operations are performed and the S.PGS
instruction ends.
• The output value (BW) is held.
• All of the output alarm bits (BB1, BB2, and BB3) are set to 0.
• The MHA and MLA of alarm detection (ALM) are set to 0.
• The control mode (MODE) is set to MAN.
0
The loop runs. When the loop runs, "SV count-up processing (3)" is performed.
Output type
Hold type
Return type
Cyclic type
Control mode (MODE)
AUT, CAB
CAS, CCB, CSV
MV
PGS
operation
SV<SV1
MV1
SV
n-1
SV<SV
n
Processing at SV'>SV
n
0: Mode shift
MAN
MAN
No mode shift
SV
Last value
0
0
MV
Last value
Last value
MV1
Restart method
After SV setting, change to
the MAN
AUT mode.
Change to the MAN
AUT
mode.
Automatic restart
Condition
Manual
Automatic
MAN, CMB, CMV, LCM, LCA, LCC
AUT, CAB, CAS, CCB, CSV
BW
BB2, MHA
BB3, MLA
BW
BB2, MHA
BB3, MLA
MV
PGS
>MH
MV
n
0
0
MV
n
=MH
1
0
MV
PGS
<ML
MV
n
0
0
MV
n
=ML
0
1
Others
MV
n
0
0
MV
n
=MV
PGS
0
0
MV
n
-
MV
n-1
SV
n
-
SV
n-1
×(SV’-SV
n-1
)+MV
n-1
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......