1296
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■
Input data
■
Block memory
■
Operation constant
Operand: (s1)
Device
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
E1
Input value
-999999 to 999999
Single-precision
real number
User
+2
e1
Operation
control signal
0: Dead time
1: No dead time
16-bit unsigned
binary
User
Operand: (d1)
Device
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
BW
Output value
-999999 to 999999
Single-precision
real number
System
+2
BB
BB1
Data sufficiency
bit
0: Data sufficient
1: Data insufficient
16-bit unsigned
binary
System
Operand: (s2)
Device
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
ST
Data sampling
interval
0 to 999999
Set a value within the following range.
Single-precision
real number
1.0
User
+2
SN
Sampling count
0 to 48
16-bit unsigned
binary
0
User
+3
+4
Ys
Output initial
value
-999999 to 999999
Single-precision
real number
0.0
User
+5
OCHG
Initial output
switching
0: Output E1 when e1 has changed from 1 to 0 SN times.
1: Output Ys up to SN.
16-bit unsigned
binary
0
User
b15
b0
...
e1
b15
b0
BB1
...
©
T
ST
<=32767
b15
b0
...
OCHG
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......