474
6 BASIC INSTRUCTIONS
6.6 Data Conversion Instructions
Processing details
• These instructions store the binary value, corresponding to the bit which is set to 1 in the 2
(n)
bit data in the device specified
by (s), in the device specified by (d).
• Specify a value 1 to 8 for (n).
• When (n)=0, no processing is performed and the values in the device specified by (d) remain unchanged.
• A bit device is treated as 1 bit, and a word device is treated as 16 bits.
• When two or more bits are 1, the upper bit position is used for processing.
Operation error
Error code
(SD0)
Description
3401H
The value specified by (n) is out of the range, 0 to 8.
The bits in the 2
(n)
bit data in the device specified by (s) are all 0s.
1 1 0
(d)
7
0
8
6 5 4 3 2 1 0
0
1 0 0 0 0 0 0
(s)
=6