2084
APPX
Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions
I-PD control (SIPD), blend PI control (SBPI)
Offset
Instruction
used
Item
Name
Recommended
range
Data type
Set by
SIPD
SBPI
+1
Shared
among the
instructions
MODE
Control mode
0 to FFFFH
16-bit unsigned
binary
User/system
User/system
+3
ALM
Alarm detection
0 to FFFFH
16-bit unsigned
binary
User/system
User/system
+4
INH
Disable alarm
detection
0 to FFFFH
16-bit unsigned
binary
User/system
User/system
+10
+11
S.PHPL
PV
Process value
RH to RL
Single-precision real
number
System
System
+12
+13
S.OUT1
MV
Manipulated value
-10 to 110 [%]
Single-precision real
number
User/system
User/system
+14
+15
S.IPD/S.BPI
SV
Set value
RL to RH
Single-precision real
number
User
User
+16
+17
S.IPD/S.BPI
DV
Deviation
-110 to 110 [%]
Single-precision real
number
System
System
+18
+19
S.OUT1
MH
Output upper limit
value
-10 to 110 [%]
Single-precision real
number
User
User
+20
+21
S.OUT1
ML
Output lower limit
value
-10 to 110 [%]
Single-precision real
number
User
User
+22
+23
S.PHPL/
S.IPD/S.BPI
RH
Engineering value
upper limit
-999999 to 999999
Single-precision real
number
User
User
+24
+25
S.PHPL/
S.IPD/S.BPI
RL
Engineering value
lower limit
-999999 to 999999
Single-precision real
number
User
User
+26
+27
S.PHPL
PH
Upper limit alarm
value
RL to RH
PL < PH
Single-precision real
number
User
User
+28
+29
S.PHPL
PL
Lower limit alarm
value
RL to RH
PL < PH
Single-precision real
number
User
User
+30
+31
S.PHPL
HH
Upper upper limit
alarm value
RL to RH
PH
HH
Single-precision real
number
User
User
+32
+33
S.PHPL
LL
Lower lower limit
alarm value
RL to RH
LL
PL
Single-precision real
number
User
User
+38
+39
S.IN
Filter coefficient
0 to 1
Single-precision real
number
User
User
+40
+41
S.PHPL
HS
Upper/lower limit
alarm hysteresis
0 to 999999 [%]
Single-precision real
number
User
User
+42
+43
S.PHPL
CTIM
Variation rate
alarm check time
0 to 999999 [s]
Single-precision real
number
User
User
+44
+45
S.PHPL
DPL
Variation rate
alarm value
0 to 100 [%]
Single-precision real
number
User
User
+46
+47
S.IPD/S.BPI
CT
Control cycle
0 to 999999 [s]
Single-precision real
number
User
User
+48
+49
S.OUT1
DML
Output variation
rate limit value
0 to 100 [%]
Single-precision real
number
User
User
+50
+51
S.IPD/S.BPI
DVL
Deviation limit
value
0 to 100 [%]
Single-precision real
number
User
User
+52
+53
S.IPD/S.BPI
P
Gain
0 to 999999
Single-precision real
number
User
User
+54
+55
S.IPD/S.BPI/
S.OUT1
Integral constant
0 to 999999 [s]
Single-precision real
number
User
User
+56
+57
S.IPD/S.BPI
D/SDV
Derivative
constant/DV
cumulative total
D: 0 to 999999 [s]
Single-precision real
number
User
SDV:
-999999 to 999999 [%]
Single-precision real
number
System
+58
+59
S.IPD/S.BPI
GW
Gap width
0 to 100 [%]
Single-precision real
number
User
User
+60
+61
S.IPD/S.BPI
GG
Gap gain
0 to 999999
Single-precision real
number
User
User
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......