7 APPLICATION INSTRUCTIONS
7.4 Structure Creation Instructions
565
7
■
Applicable devices
*1 Devices other than F can be used.
• In safety programs executed by the Safety CPU, only the following safety devices and constants can be used.
Processing details
• When the FCALL (P) instruction is executed, this instruction executes non-execution processing
*2
of the subroutine
program of the pointer (P). The FCALL(P) instruction can disable the execution of the subroutine program specified by a
pointer in the same program file or the subroutine program specified by a global pointer.
*2 Non-execution processing is the same as the processing performed by each coil instruction with the condition contact set to off.
• The operation results of individual coil instructions after the end of non-execution processing are as follows regardless of
on/off of the condition contact.
• The FCALL(P) instruction is used in combination with the CALL(P) instruction. If the FCALL(P) instruction is not used in
combination with the CALL(P) instruction, non-execution processing of the subroutine program is not performed even if the
execution command is turned off, and therefore the output status of each coil instruction is retained.
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
(P)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K,
H
E
$
(P)
(s1)
(s5)
Operand
Bit
Word
Constant
SA\X, SA\Y, SA\M, SA\SM, SA\B
SA\T, SA\ST, SA\C, SA\D, SA\W, SA\SD
K, H
(s)
A: Main routine program
B: Subroutine program
(1) Non-execution processing is performed when the command of the
FCALL(P) instruction changes from on to off.
Device used for operation
Operation result (device status)
High-speed timer, low-speed timer
Set to 0
High-speed retentive timer, low-speed retentive timer, counter
Maintains the current status.
Device in OUT instruction
Forcibly turned off.
Device in the SET, RST, SFT(P), or basic/application instruction
Maintains the current status.
PLS or pulse instruction (
P)
Performs the same processing as when the condition contact
is off.
FCALL (P)
END
(P)
RET
(1)
A
B
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......