1704
20 SERIAL COMMUNICATION INSTRUCTIONS
20.10 Clearing Receive Data
Precautions
• The following table summarizes the processes that take place if another instruction is issued while the ZP.CSET instruction
is active or the ZP.CSET instruction is issued while another instruction is active with the same channel.
*1 The G(P).CPRTCL instruction is not available with the same channel as for the Z(P).CSET instruction because it uses a communication
protocol different from the one used by the ZP.CSET instruction. If the above instruction is used with the same channel as for the
G(P).CPRTCL instruction, a communication protocol setting error (7FF2H) will occur.
• The local device and the file register for each program are not available for setting data.
Operation error
Instruction to execute
concurrently
Possibility of
concurrent execution
Handling for concurrent execution
G(P).ONDEMAND
A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
Concurrent execution is, however, possible if they use different channels.
G(P).OUTPUT
G(P).PRR
G(P).BIDOUT
G(P).BIDIN
G.INPUT
See the right
• If the G.INPUT and ZP.CSET instructions are issued in this order
A dedicated instruction concurrent execution error (7FF0H) occurs in the ZP.CSET
instruction.
Concurrent execution is, however, possible if they use different channels.
• If the ZP.CSET and G.INPUT instructions are issued in this order
Concurrent execution is possible.
ZP.CSET
The instruction is ignored and does not start processing until the active instruction
completes.
Concurrent execution is, however, possible if they use different channels.
G(P).PUTE
G(P).GETE
Z.BUFRCVS
G(P).SPBUSY
ZP.UINI
A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
Error code
((s2)+1)
Description
7000H to 7FFFH
MELSEC iQ-R Serial Communication Module User's Manual (Application)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......