11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1321
11
■
Tracking processing (2)
• The set value (SV) is inversely transformed from the engineering value and SVn' is calculated (refer to the following
expression).
• Tracking processing is performed when all of the following conditions are satisfied.
• If the set value (E2) is the upper loop MV, the TRKF of the disable alarm detection (INH) of the upper loop is set to 1.
■
MV correction (3)
The instruction calculates the deviation (DV) based on the input value (E1) and the set value (SVn') after tracking, and then
calculates the MV correction value (MV').
• The deviation (DV) is calculated under the following conditions.
• The MV correction value (MV') is calculated under the following conditions.
■
MV output (4)
The manipulated value (MV (BW)) is calculated under the following conditions.
■
Two-position (on/off) control (5)
The BB operation result (BB1) is output under the following conditions.
■
Loop stop processing (6)
The following processing is performed according to the SPA status of the alarm detection (ALM).
■
Control cycle determination (7)
• If the specified control cycle is not reached, the following processing is performed.
• If the specified control cycle is reached, "SV setting processing (1)" is performed.
• The tracking bit (TRK) is set to 1.
• The set value (E2) is used.
• The control mode (MODE) is set to any of the following: MAN, AUT, CMV, CMB, CAB, LCM, LCA, or LCC.
E2 = SV
n
'
Condition
DV
Direct action (PN = 1)
E1-SV
n'
Reserve action (PN = 0)
SV
n
' - E1
Condition
MV'
DV
HS0
100%
DV
-HS0
0%
-HS0<DV<HS0
Last value (BW value)
Condition
BW
CMV, MAN, CMB, LCM
BW=MV
n
CSV, CCB, CAB, CAS, AUT, LCC, LCA
BW=MV'
MV
n
=BW
Condition
BB1
|BW|
50%
1
|BW| < 50%
0
SPA status
Processing details
1
The loop stops. When the loop stops, the following operations are performed and the S.ONF2 instruction ends.
The output value (BW) is held.
• The control mode (MODE) is set to MAN.
The output result (BB1) value is set to 0.
0
The loop runs and "control cycle determination processing (7)" is performed.
Control mode (MODE)
Processing
CSV, CCB, CAB, CAS, AUT, LCC,
or LCA
The output value (BW) is held and the S.ONF2 instruction ends.
MAN, CMB, CMV, or LCM
"Three-position (on/off) control (5) is processed assuming that the output value (BW) equals the manipulated value
(MV).
SV
n
'=
×(SV
n
-RL)
RH-RL
100
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......