13 SFC PROGRAM INSTRUCTIONS
13.1 SFC Control Instructions
1415
13
Setting data
■
Description, range, data type
■
Applicable devices
Processing details
• These instructions check whether the specified block is active or not.
• The status (on or off) of each contact will be as follows depending on the status (active or inactive) of the specified block.
• Specify the block No. within the range of 0 to 319. If the block No. specified is out of range, both of the normally open
contact and normally closed contact turn off.
• Execute the instruction only when an SFC program exists (SM320 is on) and SM321 is on.
Precautions
• When no SFC program exists (SM320 is off) or SM321 is off, the status (on or off) of the contact will be as follows:
Operation error
There is no operation error.
Operand
Description
Range
Data type
Data type (label)
(s)
Device used as a contact
Bit
ANY_BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
(BL
)
X, Y, M, L,
SM, F, B, S,
SB, FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(s)
Status of the specified block
Contact of the normally open contact
instruction
Contact of the normally closed contact
instruction
Active
On
Off
Inactive
Off
On
Specified block No.
Contact of the normally open contact
instruction
Contact of the normally closed contact
instruction
0 to 319
Off
On
Less than 0, 320 or more (out of range)
Off
Off
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......