7 APPLICATION INSTRUCTIONS
7.12 Data Control Instructions
873
7
Processing details
• These instructions scale the scaling conversion data (32-bit data) in the device specified by (s2) on the basis of the input
value in the device specified by (s1), and stores the operation result in the device specified by (d). Scaling conversion is
performed based on the scaling conversion data stored in the device specified by (s2) and later.
• If the operation result is not an integer, the first decimal place is rounded off.
• Set the X coordinate data of the scaling conversion data in ascending order.
• Set the value in (s1) within the range of the scaling conversion data (device value in (s2), (s2)+1).
• If two or more points indicate the same X coordinate, the Y coordinate value of the largest point number is output.
• Specify a value from 1 to 4294967295 for the number of coordinate points of the scaling conversion data specified by (s2).
Setting item (n is the number of coordinate points specified
by (s2).)
Device assignment
Number of coordinate points
(s2)+1, (s2)
Point 1
X coordinate
(s2)+3, (s2)+2
Y coordinate
(s2)+5, (s2)+4
Point 2
X coordinate
(s2)+7, (s2)+6
Y coordinate
(s2)+9, (s2)+8
Point n
X coordinate
(s2)+4n-1, (s2)+4n-2
Y coordinate
(s2)+4n+1, (s2)+4n
Y
X
(d)
(s1)
Point 2
Point n-1
Point n
Point 1
Operable range
Operation error
Operation error
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......