15 NETWORK COMMON INSTRUCTIONS
15.2 CC-Link Dedicated Instructions
1533
15
Processing details
• These instructions read the number of words of data specified by (s1)+4 from the start device of the own station specified
by (s2), and write the data in the device in the target station specified by (s1)+2 and (s1)+3. Specify the target station in
(s1)+1. Upon completion of writing the data, the completion device specified by (d) turns on.
• The execution status and the completion status of the RIWT instruction can be checked with the completion device (d) and
the completion status indication device (d)+1.
• The following figure shows the execution timing of the RIWT instruction.
• Completion device (d)
This device turns on during END processing of the scan where the RIWT instruction completes, and turns off during the next END processing.
• Completion status indication device (d)+1
This device turns on or off depending on the completion status of the RIWT instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the RIWT instruction completes, and turns off during the next
END processing.
• When completed successfully
RIWT
(s2)
(s1)+2
(s1)+3
Send buffer
CPU module
CPU module
Network module
Network module
[Own station]
[Target station]
END
0
END
0
END
0
END
0
END
0
END
0
END
0
END
0
END
0
END
0
OFF
OFF
OFF
OFF
ON
ON
OFF
RIWT
3000
3000
Sequence scan
Start contact
CPU module on
the own station
CPU module on
the target station
Network
module
Network
module
Completion device
(d)
Completion status
indication device
(d)+1
Device where the
write data is stored
(s2)
Sequence scan
Device for storing
the write data
(s1)+2, (s1)+3
1 scan
Send buffer
Receive buffer
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......