11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1241
11
■
Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+1
MODE
Control mode
0 to FFFFH
16-bit unsigned
binary
8H
User/
system
+3
ALM
Alarm detection
0 to FFFFH
SPA
0: Loop RUN
1: Loop STOP
DVLA, MHA, MLA
0: No alarm
1: Alarm
16-bit unsigned
binary
4000H
User/
system
+4
INH
Disable alarm
detection
0 to FFFFH
TRKF
0: Tracking not set
1: Tracking set
ERRI, DVLI, MHI, MLI
0: Alarm detection enabled
1: Alarm detection disabled
16-bit unsigned
binary
4000H
User/
system
+14
+15
SV
Set value
RL to RH
Single-precision
real number
0.0
User
+16
+17
DV
Deviation
-110 to 110 [%]
Single-precision
real number
0.0
System
+22
+23
RH
Engineering
value upper limit
-999999 to 999999
Single-precision
real number
100.0
User
+24
+25
RL
Engineering
value lower limit
-999999 to 999999
Single-precision
real number
0.0
User
+46
+47
CT
Control cycle
0 to 999999 [s]
Set a value within the following range.
Single-precision
real number
1.0
User
+50
+51
DVL
Deviation limit
value
0 to 100 [%]
Single-precision
real number
100.0
User
+52
+53
P
Gain
0 to 999999
Single-precision
real number
1.0
User
+54
+55
I
Integral constant
0 to 999999 [s]
Single-precision
real number
10.0
User
+56
+57
D
Derivative
constant
0 to 999999 [s]
Single-precision
real number
0.0
User
+58
+59
GW
Gap width
0 to 100 [%]
Single-precision
real number
0.0
User
+60
+61
GG
Gap gain
0 to 999999
Single-precision
real number
1.0
User
+62
+63
MVP
MV internal
operation value
-999999 to 999999 [%]
Single-precision
real number
0.0
System
b15
b9
b10
b1
b2
b3
b4
b5
b6
b7
b8
b0
CMV
CSV
LCM
LCA
LCC
MAN
AUT
CAS
CMB
CAB
CCB
...
b15b14
b2 b1 b0
MLA
MHA
DVLA
SPA
...
b15
b13
b2 b1 b0
MLI
MHI
DVLI
TRKF
ERRI
...
...
©
T
CT
<=32767
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......