11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1345
11
■
Input data
■
Block memory
■
Operation constant
■
Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
■
Execution cycle (
T)
Set the execution cycle (
T) in SD816 and SD817 in single-precision real number.
Operand (s1)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
E1
Output set value
-999999 to 999999 [%]
Single-precision
real number
User
+2
+3
E2
Output control
value
-999999 to 999999 [%]
Single-precision
real number
User
+4
e1
Mode switching
signal
0: Manual mode
1: Automatic mode
16-bit unsigned
binary
User
Operand (d1)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
BW
Output value
-999999 to 999999 [%]
Single-precision
real number
System
Operand: (s2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
T
Lag time
0 to 999999 [s]
Single-precision
real number
1.0
User
+2
+3
a
Lag band
0 to 999999 [%]
Single-precision
real number
1.0
User
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
Xq
Initial deviation
value
Single-precision
real number
1.0
System
+2
+3
Xp
Deviation
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......